Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/01/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) USE CORRECT SIZE 2 HOLE STRAPS ON COPPER OVERSIZED STRAPS DO NOT SUPPORT PIEP. 2.) A WOOD SCREW THOUGH ABS PLUG NOT APPROVED ABS MAY NOT BE DRILLED OR TAPPED. USE APPROVED COUNTER SUNK TAPPED CLEAN OUT PLUG WITH APPROVED SCREW. 3.) PROVIDE INSPECTION HISTORY FOR INTERMEDIATE 4.) PROVIDE CERTIFICATION FOR RPBP. |