Permit: T00CM01622

Parcel: 132169280

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00CM01622

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
03/01/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) USE CORRECT SIZE 2 HOLE STRAPS ON COPPER OVERSIZED STRAPS DO NOT SUPPORT PIEP. 2.) A WOOD SCREW THOUGH ABS PLUG NOT APPROVED ABS MAY NOT BE DRILLED OR TAPPED. USE APPROVED COUNTER SUNK TAPPED CLEAN OUT PLUG WITH APPROVED SCREW. 3.) PROVIDE INSPECTION HISTORY FOR INTERMEDIATE 4.) PROVIDE CERTIFICATION FOR RPBP.