Permit: T00CM01588

Parcel: 125071520

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T00CM01588

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2001 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
OK TO CLEAR TEMP POWER
UNITS 500N-510 N
STRAP GROUNDING CONDUCTOR
PLACE ADDRESSES ON UNITS
CALL FOR FINAL AFTER POWER CHECK
12/19/2000 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*
OK CABLE DROP AND METER BUT NO POWER
GROUNDING ELECTRODE CONDUTOR MUST BE UNSPLICED OR SPLICED BY MEANS SPECIFIED BY N.E.C. 250-50
ALSO APPLY ANTI OXIDENT COMPOUND ON ALUMIIMUM FEEDER TO UNITS, BOTH ENDS
PRIOR TO NEXT INSPECTION HAVE PLANS, PERMITS ON SITE