Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 10/12/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* PUSH IN PLASTIC BUSHINGS NOT LISTED FOR WIRING TERMINATION TO BOX MUST HAVE TABS TO GRIP ROMEX ALL SWITCHES IN PLASTIC BOXES TO BE GROUNDED PIGTAIL GROUND WIRES FOR SWITCHES FLEX IN FIREWALLS NEED TO HAVE INSULATED ENDS TO PROTECT ROMEX FROM ABRASION |