Permit: T00CM01542

Parcel: 140410570


Addresses:

3250 E VALENCIA RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/26/2000 PLUMBING - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS MADE
10/20/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
BACKFLOW PROTECTION NOT COMPLETE
GAS EQUIPMENT NEEDS TO BE HOOKED UP
3 COMP SINK
1. VEGETABLE PREP SINK SPLASHES
2. INSTALL 2" FLOW CONTROL AND VENT ABOVE OVERFLOW
CRITICAL LEVEL ON URINAL MINIMUM 6" ABOVE TOP OF URINAL
CONDENSATE TRAP INLET AND OUTLET AT SAME LEVEL PLEASE PROVIDE 2 PIPE DIAMETER DIFFERENCE
10/16/2000 PLUMBING - FINAL Not ready for Inspection NOT READY AT THIS TIME
COURTESY WALK THRU TO HEAD OFF ANY PROBLEMS