Permit: T00CM01522

Parcel: 14027048A


Addresses:

2850 E GANLEY RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/29/2000 PLUMBING - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS MADE
RPBP CERTIFICATION OK
OK FOR C OF O PENDING ANY OTHER INSPECTIONS
09/26/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1. NEED TO SEE CERTIFICATION FOR RPBP
2. NO FITTING MAY BE TIED IN BETWEEN METER AND RPBP
3. L-4 INDICTES IRRIGATION BACKFLOW PREVENTER
TO BE TIED IN ON BLDG SIDE OF RPBP
4. NEED TO SEE RED LINE "AS BUILT" SHOWING RELOCATION OF WATER SERVICE, AND NORTH SIDE HOSE BIBB
5. KITCHEN SINK P-TRAP BACK PITCHED TO TRAP ARM
6. ADA URINAL 17" AFF MAX STANDARD URINAL 24" MAX
7. CRITICAL LEVEL ON FLUSHOMETER MINIMUM 6"
8. THIS LIST MAY NOT INCLUDE ALL CODE VIOLATIONS CHECK YOUR WORK