Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 03/21/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/13/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. NO PAPER WORK ON SITE CAN'T VERIFY IF YOU HAD A UFER INSPECTION. IF YU CAN'T VERIFY BY PAPER WORK LEFT ON SITE BY THE INSPECTOR YOU WILL NEED TWO GRO. RODS, DON'T BEND THEM THEY ARE TOO BE DRIVEN (IF YOU CAN'T GROUND TOO HARD THIS GROUND IS SOFT) THEN YOU MAY LAY THEM IN THE TRENCH 2. CONNECT GAS BOND TO SERV. PANEL GRD. 3. WIRES IN A CORN CLAMP AT GROUND ROD GO ON THE BACK SIDE OF THE CLAMP. 4. BOND RISE TO SERV. WITH A BONDING JUMPER. |