Permit: T00CM01521

Parcel: 126130340


Addresses:

4533 E COOPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/23/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
03/21/2001 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*
03/13/2001 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*/1. NO PAPER WORK ON SITE CAN'T VERIFY IF YOU HAD A UFER INSPECTION. IF YU CAN'T VERIFY BY PAPER WORK LEFT ON SITE BY THE INSPECTOR YOU WILL NEED TWO GRO. RODS, DON'T BEND THEM THEY ARE TOO BE DRIVEN (IF YOU CAN'T GROUND TOO HARD THIS GROUND IS SOFT) THEN YOU MAY LAY THEM IN THE TRENCH 2. CONNECT GAS BOND TO SERV. PANEL GRD. 3. WIRES IN A CORN CLAMP AT GROUND ROD GO ON THE BACK SIDE OF THE CLAMP. 4. BOND RISE TO SERV. WITH A BONDING JUMPER.