Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1. N/H BANDS NOT APPROVED FOR IPSXPL CONNECTION 2. CHANGES OF DIRECTION HORIZ X HORIZ TO BE MADE WITH WYE BRANCH OR EQUIVELENT SWEEP 3. CHANGES OF DIRECTION FROM VERTICAL TO HORIZONTAL TO BE MADE WITH WYE BRANCH OR EQUIVELENT SWEEP 4. HORIZONTAL VENTING BELOW FLOOD LEVEL RIM ALLOWED ONLY WHEN STRUCTRAL CONDITIONS WON'T ALLOW ANY OTHER WAY. INVENT FOR VENT CONNECTED TO HORIZONTAL DRAIN LINE MUST BE ABOVE ZERO |
|
| 09/15/2000 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1. NOT INSTALLED AS PER APPROVED PLAN PLEASE PROVIDE APPROVED REVISED PLAN OR INSTALL AS PER APPROVED PLAN 2. VENT MISSING ON FLOOR DRAIN CODE VIOLATION ON W/C NOTES RE CIRLINE FOR HOT WATER NOT ON PLAN PLEASE SHOW ALL FLOOR DRAIN REROUGH ON EXISTING FLOW CONTROLE FOR GREASE TRAP |