Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* OK WALLS |
|
| 11/03/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 11/01/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* PROTECT WIRE FROM PHYSICAL DAMAGE USE FITTING AT END OF CONDUIT FHA STRAPS STRAP M/C CABLE WITHIN 12" OF BOX SEAL M/C CABLE IN FITTING SEAL UNUSED OPENINGS IN BOXES USE APPROVED M/C CABLE FITTINGS TIGHT FITTING |