Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/18/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. SEAL FLOOR PENETRATIONS FOR TUB. 2. MOST ACCESS PANEL FOR COMP. FITTINGS 3. WASTE TRAP IMPROPERLY INSTALLED AT TUB NO COMP. NUT. 4. KIT. RANGE MUST BE INDICATED ON PLAN OR REMOVE CIRCUIT AT MOMENT CANNOT HAVE KIT. 5. 42" HIGH WALL NOT INSTALLED INSTALL WALL AND CIRCUITS OR REVISE PLAN. 6. REUSE MECHANICAL PLAN TO AS BUILT. 7. NAIL ALL ROUND HOLES IN TJI HANGERS. 8. REVISE PLAN FOR 200 AMP PANEL ON HOBBY ROOM AND FOR HEAT SOURCE CHANGE. NEXT FAILURE MAY BE CHAPPED A RE INSPECTION FEE. |
| 10/13/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. FILL IN NAILHOLES AT TJI'S. 2. COMPLETE MECH. DUCT. 3. SUBMIT AS BUILTS FOR APPROVAL. 4. STOPPED INSPECTION. |