Permit: T00CM01436

Parcel: 125110590


Addresses:

3566 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM01436

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/04/2000 ELECTRIC - FINAL Denied 10/04/00 STRAP EXTRA FLEX ON ROOF AC UNITS
AC UNITS OVERFUSED
GFCI RECEPTACLES NOT INSTALL ON ROOF
REPLACE OR INSTALL LAMP IN EMERGENCY LIGHT IN STAIRWAY
PULL CHAIN LIGHT FIXTURE IN CLOSET NOT ALLOWED MUST HAVE COVERED LENS
LABEL MAIN FUSED COMPARTMENT IN SWUTCH GEAR HAVE CONTR ON SITE TO VERIFY FUSE RATING IN GEAR AND TO REMOVE PANEL INSTALL KO SEAL IN OUTSIDE J BOX