Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM01436
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/04/2000 | ELECTRIC - FINAL | Denied | 10/04/00 STRAP EXTRA FLEX ON ROOF AC UNITS AC UNITS OVERFUSED GFCI RECEPTACLES NOT INSTALL ON ROOF REPLACE OR INSTALL LAMP IN EMERGENCY LIGHT IN STAIRWAY PULL CHAIN LIGHT FIXTURE IN CLOSET NOT ALLOWED MUST HAVE COVERED LENS LABEL MAIN FUSED COMPARTMENT IN SWUTCH GEAR HAVE CONTR ON SITE TO VERIFY FUSE RATING IN GEAR AND TO REMOVE PANEL INSTALL KO SEAL IN OUTSIDE J BOX |