Permit: T00CM01375

Parcel: 127130810

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM01375

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2000 FRAMING Approved IVRS - Inspection 0000*
10/09/2000 FRAMING Not ready for Inspection 1. BANG PLATE N/E BEDROOM ELECT. 2. ROMEX IN KITHCNE NOT IN A BOX S. W. E . WALL. 3. FIRE/BLOCK F/PLACE/CHASE. 4. MISSING FURNACE 3 W/HEATER FLUE. 5. MISSING COMB./RELIEF DUCTS. 6. STRAP I/P FLUE TAKE STRAIN OFF 45 DEGREE JOINT. 9. SUB PANEL NOT ON PLAN WHATS THE LOAD? 8. WEST FURNACE ROOM NO COMB/RELIEF NO FLUE. 9. BLOCK M/BATH VENT CIELING. 10. LOW GAS LINE TEST. 11. KIT. WALL NOT F/BLOCK AT SOFFIT. 12. LEAVE F/PLACE SPECS.
10/06/2000 FRAMING Not ready for Inspection IVRS - Inspection 0000*/NO PLANS OR PERMIT POSTED.