Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/12/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/JACCUZI TUB MOTOR MUST BE GFCI PROTECTED. |
| 10/10/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. NEED BATTERY OPERATED SMOKE DETECTORS IN EACH EXISTING BEDROOM--WHEN HOUSE VALUE INCREASED + $1,000. 2. ELECT SWITCH FOR FAN CANNOT BE WITHIN 5 FT OF JACCUZI TUB. 3. BATHROOM GFCI OUTLET HOT WHEN TRIPPED (LOAD AND LINE REVERSED). 4. PROVIDE LOCATION OF JACCUZI GFCI. |
| 10/06/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0920*/NO ONE HOME. NO ACCESS. |