Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2001 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 10/18/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*1.) NEED 1/4" MINIMUN HARDWARE FOR RISER. 2.) NEED BONDING DEVICES BOTH SIDES OF NIPPLE. 3.) NEED REJECTION CLIPS 4.) NEED PERMANENT METAL ADDRESS LABELS 5.) GROUND & BOND CONDUCTOR CALLED FOR #2 - #4 INSTALLED 6.) INSTALL GROUNDING AND BONDING AS PER PLAN OR PROVIDE CITY APPROVED REVISED PLANS 7.) LOOSE FITTINGS AN STRAPS ON FEEDER RUN 8.) MISSING JUNCTION BOX COVER CHECK DEVICES NEXT INSPECTION. |