Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/02/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) COPPER PLUMBING CANNOT BE IN CONTACT WITH METAL STUDS AND FRAME, PROVIDE APPROVED ISOLATORS 2) LAUNDRY TRAP WEIR MUST BE BETWEEN 6" AND 18" ABOVE FLOOR AND RISER MUST EXCEED 18" IN LENGTH 3) WATER HEATER T&P LINE MUST EXTEND OUTSIDE AND EXHASUT BETWEEN 5" AND 18" ABOVE GROUND 4) PROVIDE PROOF SHOWER VALVES ARE LISTED AS TEMP/PRESSURE BALANCED ANTI-SCALD VALVES |
| 10/25/2000 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/UNDER SLAB PORTABLE WATER LINES OK GAS LINE NOT IN. |
| 10/23/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1. PLAN CALLS FOR 3/4" COPPER MAIN WATER LINE TO MAIN HOUSE. 2. MASTER BATH IS NOT PER PLAN. REVISE PLAN TO AS BUILT OR BUILD TO PLAN 3. GAS LINE NOT IN. |