Inspection History: FRAMING
Permit Number - T00CM01316
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
03/27/2001 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
03/23/2001 | FRAMING | Not ready for Inspection | 1. 1/5 OF PLAN WALLS FOR DOUBLE TOP PLATES WALL BUILT UP WITH 7-2 X 6 TOP PLATES PROVIDE ARCHITECT AND CITY APPROVED DETAIL FOR PLATE TO WALL CONNECTIONS/AS BUILT. 2. 6 X 12 BEAMS ARE BEARING ON BUILT UP POSTS ON NORTH WALL THAT ARE SPLICED AT 8+ FOOT LEVEL AND BEARING ON SINGLE 2 X 4 STUDS AT 16" O.C. ON SOUTH WALL. 3. RAFTERS ON OVERBUILT AREA MUST BEAR ON 2X SLEEPERS/VALLEY BOARDS THE WIDTH OF RAFTERS CUT. 2 X 8 NOTE 7. |