Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - PROGRESS
Permit Number - T00CM01307
Inspection Description - MECHANICAL - PROGRESS
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* | |
08/25/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* HOLE SOW CUT THROUGH SLABS NEED TO SEAL REAR OF HOLE BETWEEN CHASE AND WALL. DON'T KNOW IF 5/8" EXTERNAL COVERING IS GOING TO SEAL ENTIRE OPENING OK TO CONTINUE |
|
08/23/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* | |
08/22/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* | |
08/21/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* | |
08/18/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* PARTIAL OUTSIDE PROGRESSING SUSPENDING TYPE I DUCT ON EXTERNAL WALL |
|
08/16/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* EXHAUST DUCT DEVELOPING UP THRU RATED CHASE |
|
08/14/2000 | MECHANICAL - PROGRESS | Approved | ||
08/09/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* PARTIAL RATED CHASE NOT ALLOWING 3" CLEARANCE TO 16 GAU BLK IRON DUCT ON ALL SIDES NEED RATED CLEAN OUT ACCESSES AT ALL 90 DEGREE BENDS POSSIBLE USE FIREMASTER OR FLAME CHECK |