Permit: T00CM01307

Parcel: 11720016E

Inspection Status: Partial Approval

Inspection History: MECHANICAL - PROGRESS

Permit Number - T00CM01307

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/30/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
08/25/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
HOLE SOW CUT THROUGH SLABS NEED TO SEAL REAR OF HOLE BETWEEN CHASE AND WALL. DON'T KNOW IF 5/8" EXTERNAL COVERING IS GOING TO SEAL ENTIRE OPENING
OK TO CONTINUE
08/23/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
08/22/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
08/21/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
08/18/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
PARTIAL OUTSIDE PROGRESSING
SUSPENDING TYPE I DUCT ON EXTERNAL WALL
08/16/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
EXHAUST DUCT DEVELOPING UP THRU RATED CHASE
08/14/2000 MECHANICAL - PROGRESS Approved
08/09/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
PARTIAL
RATED CHASE NOT ALLOWING 3" CLEARANCE TO 16 GAU BLK IRON DUCT ON ALL SIDES
NEED RATED CLEAN OUT ACCESSES AT ALL 90 DEGREE BENDS
POSSIBLE USE FIREMASTER OR FLAME CHECK