Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 09/26/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* WILL NEED VERIFICATION OF RE INSPECTION FEE PAID GROUNDS NOT MADE UP SEE EXTERIOR AND OTHER RECEPTACLES NEED TO USE PROPER TOOL FOR CRIMP SLEEVE. PROPER TOOL IS LISTED ON BOX NEED TO HAVE GROUND TAILS READY FOR SWITCH CONNECTION |
|
| 09/21/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0935* NEED FHA STRAPS THROUGH OUT UNITS A RE FEE IS DUE BEFORE NEXT INSPECTION |
|
| 09/19/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* NEED BOX AT BATH LIGHT OR LISTED AND APPROVED FIXTURE NEED FHA STRAPS 24" SEPERATED IN FIREWALL TIGHTEN GROUND SCREWS SNAP BUSHING INTO BOXES |
|
| 09/14/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* REMOVE INSULATION FOR IN SPECTION OF ELECTRICAL INSULATION OF ROMEX TO BE 1/4" AT LEAST IN BOX MAKE UP BATH FANS NEED BOX AT BATH LIGHT TIGHTEN GROUND SCREWS MAKE UP PANEL 24" SEPERATION IN FIREWALL MAKE UP ALL OUTSIDE BOXES FIRE WALL PENETRATIONS CK WITH BUILDING INSPECTOR GROUND METAL BOXES |