Permit: T00CM01198

Parcel: 11308089B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/27/2000 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/26/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
WILL NEED VERIFICATION OF RE INSPECTION FEE PAID
GROUNDS NOT MADE UP SEE EXTERIOR AND OTHER RECEPTACLES
NEED TO USE PROPER TOOL FOR CRIMP SLEEVE. PROPER TOOL IS LISTED ON BOX
NEED TO HAVE GROUND TAILS READY FOR SWITCH CONNECTION
09/21/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0935*
NEED FHA STRAPS THROUGH OUT UNITS
A RE FEE IS DUE BEFORE NEXT INSPECTION
09/19/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
NEED BOX AT BATH LIGHT OR LISTED AND APPROVED FIXTURE
NEED FHA STRAPS
24" SEPERATED IN FIREWALL
TIGHTEN GROUND SCREWS
SNAP BUSHING INTO BOXES
09/14/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
REMOVE INSULATION FOR IN SPECTION OF ELECTRICAL
INSULATION OF ROMEX TO BE 1/4" AT LEAST IN BOX
MAKE UP BATH FANS
NEED BOX AT BATH LIGHT
TIGHTEN GROUND SCREWS
MAKE UP PANEL
24" SEPERATION IN FIREWALL
MAKE UP ALL OUTSIDE BOXES
FIRE WALL PENETRATIONS CK WITH BUILDING INSPECTOR
GROUND METAL BOXES