Permit: T00CM01171

Parcel: 141153120

Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/13/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - APPROVED AS NOTED: TOP PLATE DOUBLER MUST LAP MINIMUM 48 AT JOINT OF 1ST TOP PLATE AT INTERSECTION OF MASTER BEDROOM SOUTH WALL WITH BATHROOM WALL. BIG GAP IN DOUBLER. BREAK IN TOP PLATE. PLEASE CORRECT. WILL RE-CHECK AT INTERMEDIATE INSPECTION.
04/10/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - DENIED - 1. TOP PLATE DOUBLER MUST LAP MINIMUM 48 AT JOINT OF 1ST TOP PLATE. 2. GARAGE SHEAR TRANSFER NOT PER 17/SD3. 3. ALL HOLD-DOWNS MUST BE FULLY NAILED. 4. GABLE END TRUSS IS NOT CLIPPED TO WALL BELOW. 5. GIRDER TRUSS REQUIRES MINIMUM DOUBLE STUD BELOW. 6. NO TRUSS CALCULATIONS ON SITE.
04/10/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*