Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/15/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* 1) NEED TO SEE FIRST FLOOR CLOSET RINGS 2) REMEMBER PLUMBERS TAPE IA NOT APPROVED FOR MEETING MINIMAL STRAPPING REQUIREMENTS |
| 02/14/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1) WHERE VENTS CONNECT TO A HORIZONTAL DRAIN THE VENT INVERT MUST BE ABOVE THE DRAINAGE CENTERLINE |
| 02/12/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* NEED TO PROVIDE AT LEAST MINIMAL SUPPORT AND BRACING ON DRAINS AND WATER LINES. |
| 02/09/2001 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/08/2001 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |