Permit: T00CM01140

Parcel: 136049100


Addresses:

2501 S PERILLO DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/27/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/09/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
02/27/2001 ELECTRIC - INTERMEDIATE Denied
02/16/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*/LOCKED NO ACCESS.
02/09/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. ENGINEER REPORT ON CUT TRUSSES WILL BE REQUIRED AT FINAL INSPECTION. 2. DETAILS CALLLED OUT ON FRAMING PLAN DO NOT EXIST (IE 25/A12, 26/A12) ADDED DETAILS MUST BE COT APPROVED.
01/11/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
12/12/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. WATER TEST ALL DRAIN LINES. 2. SECURE HOSE BIB AT WALL TO OUTSIDE. 3. PROTECT PLUMB AT PLATES. 4. MOVE WIRES AWAY FROM CAN LIGHTS. 5. SECURE 4 GANG BOXES. 6. CHECK ON VTR. 7. NEED LEGIBLE PLANS. 8. NEED TFD APPROVAL FOR FIRE SPRINKLER SYSTEM.
08/31/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
08/30/2000 ELECTRIC - INTERMEDIATE Denied 1. THERE ARE TOO MANY LOOPS ON YOUR GROUNDING ELECTRICAL. 2. GO FROM GROUND CODE TO SERVICE PANEL NOT TO BONDING JUMPER (USE BONDING JUMPER TO BOND BOX AND CONDUIT). 3. LOOSE RISER.
07/14/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection