Permit: T00CM01133

Parcel: 13414001K

Inspection Status: Correction Required

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/12/2000 MECHANICAL - ABOVE CEILING Correction Required ADDTL COMMS - 1. STRAP FLEX DUCT OFF OF GRID 2. STRAPS SHOULD BE MIN. 4 APART 3. WILL CHECK CORRECTIONS ON FINAL DO NOT INSTALL TILES YET