Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM01096
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
06/13/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - FINAL SUBJECT TO CORRECTION OF PREVIOUS INSPECTION 1. BREAKERS TO BE PER MANUFACTURES LISTING 2. NEED RIGID SUPPORT FOR ROOF ICE MACHINE SWITCH 3. OUTDOOR LIGHTS TO MEET OUTDOOR LIGHTING ORDAINCE OK TEMP C OF O PER BOND #1205106 | |
06/13/2000 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C/O | |
06/09/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. NEED RIGID SUPPORT ON ICE MACHINE ROOF VENT SWITCH 2. BREAKER TO BE PER MANUFACTURES LISTING 3. OUTDOOR LIGHT TO MEET LIGHTING ORDANICE 8510 SEC 5 AND TABLE 5 | |
06/09/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
06/06/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. GROUND SWITCHES 300-9 2. TIME CLOCK DRIVE THRU WINDOW 3. ELECTRIC BOX NEXT TO PANEL NOT MADE UP 4. VERIFY EXIT SIGNS WITH BUILDING INSPECTOR 5. SEAL HOLES IN PANEL 6. BREAKER TO BE PER MANUFACTURES LISTING 7. SEAL HOLE IN ROOF GUTTER 8. SEAL HOLE IN A/C DISCONNECT 9. BOND GUTTER DISCONNECTS 10 SUPPORT T-STRAP WALK IN BOX SEAL TIGHT | |
06/06/2000 | ELECTRIC - FINAL | Denied | DENIED |