Permit: T00CM01093

Parcel: 11204407A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/11/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/30/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
DISC SW AND STARTER BY CHILLER IN VIOLATION OF WORKING CLEARANCE 30" HORIZONTAL AND 36" IN FRONT 110-26 NEC
3/4" EMT CONDUIT INSTALLED IN FRONT OF DISCONNECT BY COOLING TOWER IS A TRIP
HAZARD AND VIOLATES WORKING CLEANRANCE
110-26 NEC