Inspection History: ELECTRIC - FINAL
Permit Number - T00CM01093
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/30/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* DISC SW AND STARTER BY CHILLER IN VIOLATION OF WORKING CLEARANCE 30" HORIZONTAL AND 36" IN FRONT 110-26 NEC 3/4" EMT CONDUIT INSTALLED IN FRONT OF DISCONNECT BY COOLING TOWER IS A TRIP HAZARD AND VIOLATES WORKING CLEANRANCE 110-26 NEC |