Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
10/05/2000 SHEET ROCK NAILING Approved IVRS - Inspection 0000*
10/02/2000 SHEET ROCK NAILING Denied COVERED WITHOUT APPROVAL. REFEE. SECURE TO MISSED STUDS ALSO REMOVE TAPE AT GARAGE CEILING AT SEAM 12" FROM NORTH WALL.
09/27/2000 SHEET ROCK NAILING Partial Approval IVRS - Inspection 0000*/TAPE HOUSE OK NOT GARAGE. 1. THE GARAGE DOUBLE CEILING DRYWALL HAS EDGES ALIGNED AT NORTH SIDE 8" RIPPER. 2. 5/8 FIRE RATED DRYWALL ON WALLS MUST BE SECURED AT TOP EDGES AT 7" O.C. WITH 6D. NAILS OR 1 7/8" LONG. 3. GARAGE FIRE RATED DRYWALL MUST BE FASTENED TO STUDS SPACED 16" O.C. 3. MISSED.
09/25/2000 SHEET ROCK NAILING Denied IVRS - Inspection 0175*/1. GARAGE FIRE RATED DOUBLE CEILING SEAMS CANNOT OVERLAP ON SAME CEILING JOIST. LEAVE ONE 4X4 PANEL DOWN TO VARIFY SEAM OVERLAP. 2. FIRE RATED 5/8 TYPE X DRYWALL MUST BE SECURED WITH 1 7/8" SCREWS OR NAILS SPACED AT 7" O.C. AT ALL SUPPORTED ENDS/EDGES AND STUDS. TABLE 7B.