Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM01083
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2001 | ELECTRIC - FINAL | Approved | APPROVED OK TO CLEAR ECO CALLED IN 10AM THUR. | |
10/29/2001 | ELECTRIC - FINAL | Denied | A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION.1.) NEED A NEUTRAL TO SERVICE DISCONNECT - SEE PLAN 2.) NEED A NEUTRAL DISCONNECT LINK AT MAIN. 3.) BOND NEW NEUTRAL TERMINATION 1 UNIT TO CAN 4.) PERMANETLY & CONSPIRUOUSLY WORK "MAIN" 5.) NEED REJECTION CLIPS. 6.) PLEASE USE PODLOCK FOR C.T. CON FOR ENTRY. | |
10/10/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*LIGHTING CONTACTOR SERVICE PEDESTAL 7270 E TUCSON BLVD APPROVED FOR FINAL POWER CLEARANCE SUBJECT TO TRANSFORMER YARD FINAL. | |
10/01/2001 | ELECTRIC - FINAL | Not ready for Inspection | ||
09/27/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |