Permit: T00CM01082


Addresses:

7275 S TUCSON BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T00CM01082

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2002 MECHANICAL - ABOVE CEILING Approved
02/04/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PIPE PRESS REG. BOILER TO DAYLIGHT 1050 24" SQ. COMB GRILLS. 2.) VESTIBLE NEED ADDITIONAL ACCESS PANEL UNDER CONTROL BOX ON VAV. 3.) OK TO COVER REMAINDER OF INTERMEDIATE.
01/18/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*PARTIAL CONFIRMED ADDITIONAL ACCESS PANELS HAVE BEEN ADDED TO GRID LINE 1.5 WEST SIDE OK TO COVER.
01/15/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*STORE FRONT AREA ACCESS TO WATER VALVES, STRAINERS, ON HOT WATER LPS. PROVIDE ACCESS AS NECESSARY, WHERE ACCESS IS NECESSARY. NORTH END REST RM'S. EVAP. COOLER BE CERTAIN PLYSICAL SIZE IS GOING TO LOCATE IN ALLOWED SPACE WITH PROPER ACCESS. VESTIVULE ACCESS TO VAV #10. IS TOTALLY BLKD. SOMETHING NEEDS TO MOVE SOUTH END.
12/04/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*CHECKED HIGH PRESS DUCTS TO VAV'S BEGINNING LOW PRESS DUCTS TO LINERS PROGRESSING.
11/28/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*HWS/HWR 80 PSI. NORTH EAST LP.
11/19/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*PROVIDE ADEQUATE SUPPORT ON WATER LINES AT VAV BOXES. PROVIDE TEST ON ENTIRE SYSTEM.