Permit: T00CM01082


Addresses:

7275 S TUCSON BL


Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T00CM01082

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2001 PLUMBING - ABOVE CEILING Approved IVRS - Inspection 0000*1.) THIS INSPECTION CONCERNS THE COMBINING OF ROOF DRAIN AND OVERFLOW DRAIN FOR THE CANOPY BETWEEN GRID LINES G.H 1.5 AND 8. UNDER THE CODE ENFORCED AT THE TIME THE PLANS WERE APPROVED, THESE DRAINS COULD BE COMBINED IF Z PIPE SIZED LARGER THAN REQ'D SIZE HNTB ARCHETECTS ENGINEERS SUBMITTED PAPER WORK. APPROVING THIS INSTALLATION. 2.) OK TO COVER.
09/24/2001 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0999*1.) REVIEW TABLE 3-1 HANGERS AND SUPPORTS ESPECIALLY NOTES #1,#2,#3,#4.