Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM01082
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) PLUMBING INTERMEDIATE OK N/H DWV OK PRESSURE TEST OK ON COPPER OK TO COVER WALL. 2.) WHERE ROOF DRAIN COMBINES WITH OVERFLOW I QUESTION 1 4" ROOF DRAIN AND OVERFLOW DUMPING INTO 3" PIPE OBSTRUCTION FO FLOW 2.) NO SQ FOOTAGE OF DRAINAGE TO VERIFY SIZING. IS PIPE OVERSIZED TO ALLOW COMBINING? 3.) PROVIDE COMPLETE DATA SUPPORTING INSTALLATION. | |
10/16/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
10/03/2001 | PLUMBING - INTERMEDIATE | Partial Approval | 1.) MEDIUM PRESSURE 1/4 GAS TO BOILER OK 60# AIR TEST OK 2.) OK TO COVER. | |
09/25/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* |