Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/08/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/04/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
OK FOR TEMP C/O |
| 09/27/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL RECEIVED LETTER PERTAINING TO THE OPERATION OF THE EMERGENCY GENERATOR, WHICH WILL BE PRESENTED TO STEVE LONG. |
| 09/26/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*PARTIAL NEED TO SET UP EMERGENCY TRANSFER TEST WITH AIRPORT AND ELECTRICAL CONTRACTOR STURGEON/CANYON STATE. FOR TEMP C OF O. |
| 09/21/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*PLEASE PROVIDE LIGHTING TEST AS WELL AS REG LIGHTING IN PARKING STRUCTURE. |
| 09/19/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL OK TO ENERGIZE PANEL NECP AND DOWN ELECTRIC RM 109 COMPLETE |