Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* NOTE: HAVE ALL OF SERVICE COMPLETE FOR FINAL. TAG ALL PANELS AND INSTALL WATER BOND. CLEARANCE IN FRONT OF SERVICE TO COMPLY WITH 110-26 NEC AND WILL NEED MIN. OF 18" BETWEEN GROUNDS AND BOTTOM OF SERVICE DISCONNECTS, AS WELL AS ALL OF THE AREA PER 110-26 TO BE PERMANENT AND LEVEL | |
| 02/01/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* SHOE BOX FIXTURE OK STANDARD THHN/THNN (90 DEGREE CENTER WIRE) OK WALL PAKS SHIELDING APPROVED (LIGHT POLLUTION CODE) AND MIN OF 150 C BOND WIRING APPROVED THE FIXTURE WIRED WITH #14 SF-2 WIRE |
|
| 01/03/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | HIGH BAY LIGHTING 350 W. M.H. 4 SQ BOX, COVER, STEM AND SAFETY CHAIR OK SUPPLY WIRES 90 C- OK |
|
| 01/02/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* BOTH SIDES WALK APPROVED |