Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/29/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/28/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. COMPLETE MECH AT DROP. 2. PROVIDE FIRE BLK AT DROP 3. SKYLIGHT NOT READY. 4. STRAP RAFTER TO BEAM AT GARAGE 5. STRAP TOP PLATE TO BEAM. |
| 10/31/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. BLOCK MECH. 3 SIDES. 2. INSTALL SKYLIGHTS AT ENTRY. 3. STRAP DOUBLE TOP PLATE. 4. PROVIDE DRYWALL NAILER WEST BD RM. 5. NAIL EXTERIOR SHEATING AT 6" E.N. AND 12" FIELD. |
| 08/18/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/27/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE PRESSURE TREATED SOLE PLATES AT CONCRETE PER PLAN SHEET #4 AND UBC 2306.4 2. STRAP DOUBLE TOP PLATE TOGETHER THAT IS NOT OFFSET (WEST WALL TOP) PER UBC 2320.11.2. 3. EXISTING WINDOW IN BEDROOM ADDITION DOES NOT MEET MIN. HIEGTH REQUIREMENT 44" MAX FROM FLOOR--UBC 310.4. 4. NATURAL LIGHT MIN. REQUIREMENT FOR BEDROOM ADDITION HABITABLE SPACE IS 10% OF FLOOR AREA--UBC 1203.2. 5. PROVIDE ELECTRIC RECEPT WITHIN 6'0" OF SOUTH DOOR. EAST SIDE NEC. 210.52A (4401.2). 6. GARAGE ADDITION NOT READY AT THIS TIME. 7. EXISTING PLANS DO NOT REFLECT FIRE WALL BETWEEN GARAGE AND BEDROOM. 8. LIGHTING NOT PER PLAN. |