Permit: T00CM01024

Parcel: 13109100B


Addresses:

5837 E 26TH ST 03


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T00CM01024

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2001 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
07/23/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*1.) PROVIDE SUPPORT ON DUCT RISER IN SHAFT. 2.) ATTACH DUCT TO EXHAUST FAN UPSTAIRS 3.) PROVIDE SUPPORT ON GAS PIPE IN SOFFETT. DO NOT USE PLUMBERS TAPE TO SUPPORT GAS PIPE. 4.) ATTACH KITCHEN EXHAUST DUCT TOGETHER 5.) SUPPORT DRYER VENT CORRECT & RECALL FOR INSPECTION 6.) CABLE TV CANNOT RUN THROUGH THE "B" VENT FLASHING.