Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T00CM01023
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2000 | ELECTRIC - UNDERGROUND | Approved | ||
| 04/27/2000 | ELECTRIC - UNDERGROUND | Correction Required | ADDTL COMMS - (TEP RESPONSIBLE FOR TRENCH INSPECTION) | |
| 04/27/2000 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
| 04/26/2000 | ELECTRIC - UNDERGROUND | Correction Required | ADDTL COMMS - 1. GROUP SERVICES TOGETHER PER (1999-NEC 230-72) 2. PER 250-94 STANDARD LOCKNUTS SHALL NOT BE THE SOLE MEANS OF BONDING THE SERVICE RISER (USE BOND BUSHING OR BONDING LOCKNUT) 3. SPECIAL INSP IS ONLY APPLICABLE FOR BUILDING INSP UFER WASNT INSPECTED BY CITY OF TUCSON | |
| 04/26/2000 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999* |