Permit: T00CM01023

Parcel: 13109100B


Addresses:

5837 E 26TH ST 01


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T00CM01023

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2000 ELECTRIC - UNDERGROUND Approved
04/27/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - (TEP RESPONSIBLE FOR TRENCH INSPECTION)
04/27/2000 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*
04/26/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - 1. GROUP SERVICES TOGETHER PER (1999-NEC 230-72) 2. PER 250-94 STANDARD LOCKNUTS SHALL NOT BE THE SOLE MEANS OF BONDING THE SERVICE RISER (USE BOND BUSHING OR BONDING LOCKNUT) 3. SPECIAL INSP IS ONLY APPLICABLE FOR BUILDING INSP UFER WASNT INSPECTED BY CITY OF TUCSON
04/26/2000 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*