Inspection History Details
Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM00957
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2000 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. SOIL WATER TEST OK 2. OVERHEAD WATER DISTRIBUTION OK 3. OK TO DRYWALL 4. ALL CORRECTIONS HAVE BEEN MADE | |
06/07/2000 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. CAN NOT USE COMBO FOR HORIZONTAL TO VERTICAL DRAINAGE AT 2ND FLOOR SHOWER AND AUTO WASHER 2. MUST USE BRASS SCREWS TO ANCHOR CLOSET PHANGE 3. C.O. FOR KITCHEN SINK MUST GO ON VERTICAL NOT HORIZONTAL 4. RE-TEST SYSTEM | |
06/07/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0000* |