Permit: T00CM00916

Parcel: 115151930


Addresses:

1726 N 15TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/20/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/14/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) BATHROOM MUST HAVE A 20 AMP GFCI OUTLET WITHIN 36" OF LAVATORY ON LAVATORY WALL, WITH NO OTHER ROOM ON THAT CIRCUIT 2) FIRE BLOCK ALL WALLS AT CEILING LINE 3) SMOKE DETECTORS REQUIRED IN EACH BEDROOM, HALL AND ROOMS LEADING TO BEDROOMS LOCATED 18" FROM CORNERS 36" FROM AIR REGISTERS AND WITHIN 6 AND 12" OF CEILINGS ON WALLS OR 18" FROM WALLS ON CEILINGS, SMOKE DETECTORS MUST BE INTER CONNECTED NOTE: KITCHEN COUNTER OUTLETS MUST BE ON 2 SEPARATE GCFI PROTECTED CIRCUITS