Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM00915
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2000 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1.WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. WILL REQUIRE A C.O. WHERE DWV WASTE LINE FOR RM#135,130 EXCEEDS 135 DEGREES 4. MUST REVERSE OR REMOVE TEST WYES NO FITTING MAY BE INSTALLED WITH REVERSE FLOW 5. FLAT VENT FOR BACK TO BACK W.C. IS REVERSED. REMOVE SAN TEE AND REPLACE WITH DRAINAGE FITTING. 6. CAN NOT WET VENT DRINKING FOUNTAIN BETWEEN FLOORS 7. OK TO DRYWALL. |