Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM00915
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2000 | ELECTRIC - ABOVE CEILING | Approved | ||
04/13/2000 | ELECTRIC - ABOVE CEILING | Correction Required | ADDTL COMMS - 1. NEED GRID TILES OPEN TO SEE FIXTURES AND ELECTRICAL 2. NEED LETTER FROM ARCIT APPROVING M/C CABLE NOTE OPEN AREAS OK PLEASE RECALL FOR INSPECTION WHEN CORRECTED | |
04/13/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
04/07/2000 | ELECTRIC - ABOVE CEILING | Correction Required | ADDTL COMMS - NEC 300-11 ALL WIRING IN CEILING TO BE TIED OFF BY INDEPENDENT SUPPORTS-NOT CEILING WIRES CITY OF TUC ORD 410- ALL FIXTURES TO HAVE SEMIC SUPPORTS AND TO BE MECHANICALLY ATTACHED TO T-BAR | |
04/07/2000 | ELECTRIC - ABOVE CEILING | Denied | DENIED |