Permit: T00CM00854

Parcel: 11446908A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/02/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST FINAL OK S.T.O.I. GAS CARD AT METER SET
12/30/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
GAS LINE FOR POOL EQUIPMENT MUST HAVE APPROVED STRAPS TO SECURE GAS LINE TO WALL P-TRAP IS NOT APPROVED MATERIAL
PLDG FINAL WAS OK
ALL CORRECTIONS HAVE BEEN MADE
12/27/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
DOORS WERE LOCKED
12/21/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
WATER CLOSET MUST HAVE OPEN FRONT SEAT LESS LID
WATER HEATER P& T FLEX CAN ONLY BE 12" OF FLEX MAX
BBQ NOT INSTALLED
WATER CLOSET H.C. MUST BE MIN OF 18" FROM SIDE WALL TO CENTER OF CLOSET (ADA SPECS)
MUST CAULK LAVATORY
WATER HEATER P&T FLEX CAN ONLY BE 12" OF FLEX MAX
BBQ NOT INSTALLED
WATER CLOSET H.C MUST BE MIN OF 18" FROM SIDE WALL TO CENTER OF CLOSET (ADA SPECS)
MUST CAULK LAVATROY