Permit: T00CM00848

Parcel: 11516025B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/28/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) EXPOSED CONDUCTORS AT POWER POLE 2) GROUND JUNCTION BOX AT POWER POLES ROOF OK EXCEPT AS NOTED
02/15/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0430* NOTE: INTERIOR OK.
1) THE A/C UNIT SWITCH MUST BE MARKED WITH THE PANEL AND CIRCUITS FEEDING ITS LINE.
2) THE PUMP CIRCUIT MUST BE TAKEN OUT OF THE SWITCH. THE SWITCH MUST NOT BE USED FOR FEED THRU OR JUNCTION BOX. 3) THE SEAL FLEX CONDUIT MUST HAVE SEAL FLEX FITTINGS INSTEAD OF FLEX CONDUIT FITTINGS. CORRECT AND RECALL
01/17/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
FILL ALL UNUSED OPENINGS
SUPPORT CONDUIT AS PER CODE
CONDUIT BETWEEN LIGHTS FIX AND SUPPORT RESTROOMS RECEPTICAL TO BE GFI PROTECTED
NEED ACCESS TO POWER POLES
PUMP ILLIEGLE INSTALL TO A/C DISCONNECT
LABEL DISCONNECTS
GFI ON ROOF WITHIN 25' ON A/C UNITS