Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) EXPOSED CONDUCTORS AT POWER POLE 2) GROUND JUNCTION BOX AT POWER POLES ROOF OK EXCEPT AS NOTED | |
| 02/15/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0430* NOTE: INTERIOR OK. 1) THE A/C UNIT SWITCH MUST BE MARKED WITH THE PANEL AND CIRCUITS FEEDING ITS LINE. 2) THE PUMP CIRCUIT MUST BE TAKEN OUT OF THE SWITCH. THE SWITCH MUST NOT BE USED FOR FEED THRU OR JUNCTION BOX. 3) THE SEAL FLEX CONDUIT MUST HAVE SEAL FLEX FITTINGS INSTEAD OF FLEX CONDUIT FITTINGS. CORRECT AND RECALL |
|
| 01/17/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* FILL ALL UNUSED OPENINGS SUPPORT CONDUIT AS PER CODE CONDUIT BETWEEN LIGHTS FIX AND SUPPORT RESTROOMS RECEPTICAL TO BE GFI PROTECTED NEED ACCESS TO POWER POLES PUMP ILLIEGLE INSTALL TO A/C DISCONNECT LABEL DISCONNECTS GFI ON ROOF WITHIN 25' ON A/C UNITS |