Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* OK FIRE RATED CORRIDORS WIRES SUBJECT TO BUILDING INSPECTION |
|
| 10/30/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | OK EXCEPT FIRE RATED CORRIDORS | |
| 10/27/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* USE APPROVED CABLE/DATA SUPPORTS LET'S TALK ABOUT THE 1-HR CEILING |
|
| 10/26/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*10/26/00 SUPPORT DATA CABLE AS PER CODE HAVE BUILIDNG INSPECTOR LOOK AT FIXTURE ENCLOSURE FINISH BREAK ROOM UP AND PRESIDENT OFFICES |
|
| 10/25/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | 10/25/00 SECURE SUPPORT WIRES AT BOTH END 300-11 IDENTIFY SUPPORT WIRES IN FIRE RATED AREAS 300-11 ENCLOSE FIXTURES IN FIRE RATED CEILING REMOVE OLD BOXES AND WIRE OR SEAL |
|
| 10/24/2000 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | 10/24/00 NO NOTES |