Permit: T00CM00845

Parcel: 123061390


Addresses:

2416 E ADAMS ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/17/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
01/12/2001 BUILDING - FINAL Denied IVRS - Inspection 0920*/HOUSE LOCKED NO ACCESS.
01/11/2001 BUILDING - FINAL Denied IVRS - Inspection 0950*/NO CHANGE.
01/10/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/1. EXPOSE/PROVIDE ACCESS TO A/C LABLE. 2. SECURE A/C FLEX CONDUIT WITHIN 12" OF DISCONNECT. FUSES NOT IN. 3. INSTALL GANG DISCONNECT BARS ON MAIN BREAKER. 4. BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS. 5. GFCI OUTLETS REQUIRED WITHIN 24" OF EITHER SIDE OF KITCHEN SINK. 6. STOOP REQUIRED AT SOUTH ENTRY. NEED INSEPCTION CARD, INSULATION AND STUCCO INSTALLATION CERTIFICATES NEED COMPLETE APPROVED PLAN ON SITE. MAX 35 AMP A/C FUSE .50A INSTALLED.