Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0920*/HOUSE LOCKED NO ACCESS. |
| 01/11/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0950*/NO CHANGE. |
| 01/10/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. EXPOSE/PROVIDE ACCESS TO A/C LABLE. 2. SECURE A/C FLEX CONDUIT WITHIN 12" OF DISCONNECT. FUSES NOT IN. 3. INSTALL GANG DISCONNECT BARS ON MAIN BREAKER. 4. BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS. 5. GFCI OUTLETS REQUIRED WITHIN 24" OF EITHER SIDE OF KITCHEN SINK. 6. STOOP REQUIRED AT SOUTH ENTRY. NEED INSEPCTION CARD, INSULATION AND STUCCO INSTALLATION CERTIFICATES NEED COMPLETE APPROVED PLAN ON SITE. MAX 35 AMP A/C FUSE .50A INSTALLED. |