Permit: T00CM00817

Parcel: 123160910


Addresses:

1240 E MABEL ST #02

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/02/2000 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
11/01/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0230*/1. PROVIDE PROOF OF UFER INSPECTION OR INSTALL TWO 8' GROUND RODS A MINIMUM OF 6 FEET APART CONNECTED TO THE SERVICE PANEL WITH A CONTINUOUS #4 GROUND WIRE. 3. SERVICE RISER NOT PROPERLY BONDED. SEE N.G. C. 250-94 INSTALL BONDING RING OR BONDING BUSHING.