Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/31/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ROOF A/C DISCONNECT CANNOT BE SUPPORTED FROM SINGLE CONDUIT, PROVIDE ADDITIONAL BRACE 2) FLEX NON METALIC CONDUIT CANNOT EXCEED 6 FEET IN LENGTH TO A/C 3) 3" EXISTING WASTE VENT HAS BEEN BROKEN OFF FLUSH WITH ROOF MUST EXTEND AT LEAST 6" ABOVE ROOF 4) 3 EACH CEILING FANS HANG BELOW 7 FEET TO PADDLES |
| 05/14/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ROOF TILE NOT INSTALLED 2) GRADING AROUND HOUSE MUST HAVE TWO PERCENT SLOPE AWAY FROM HOUSE FOR FIVE FEET 3) YOU MUST PROVIDE LADDER ACCESS TO ROOF TO INSPECT ROOF TOP AND MECHANICAL UNIT ON TWO STORY HOUSE 4) TRIM CLEAN OUTS TO GRADE AND INSTALL APPROVED CAPS 5) HOLES IN EXTERIOR STUCCO AND VAPOR BARRIER 6) NO POWER ON OUTSIDE GFCI CIRCUIT 7) NO POWER ON DISPOSAL CIRCUIT 8) FURNACE GAS LINE NOT CONNECTED 9) NO PLANS/PERMIT ON SITE 10) NEXT FAILURE WILL RESULT IN REINSPECTION FEE |