Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM00766
Inspection Description - ELECTRIC - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - OK FINAL | |
05/15/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - NEED MANUFACTORS LABEL FOR PANEL CALL WHEN INSTALLED | |
05/15/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
05/12/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. 120/240 V PANEL COVER -DEADFRONT ON A 480V SYSTEM. 2. CONDUCTOR COLOR IN CORRECT NEED TO BE BROWN CITY ORDINACE 9287 210-5 NOT BLACK 3. BOND JUNCTION BOX ABOVE PANEL AND ON 2ND FLOOR 250-96A | |
05/12/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |