Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - OK FINAL |
| 05/15/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - NEED MANUFACTORS LABEL FOR PANEL CALL WHEN INSTALLED |
| 05/15/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/12/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. 120/240 V PANEL COVER -DEADFRONT ON A 480V SYSTEM. 2. CONDUCTOR COLOR IN CORRECT NEED TO BE BROWN CITY ORDINACE 9287 210-5 NOT BLACK 3. BOND JUNCTION BOX ABOVE PANEL AND ON 2ND FLOOR 250-96A |
| 05/12/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |