Permit: T00CM00728

Parcel: 126180360


Addresses:

4126 E PASEO DORADO

Inspection Status: Partial Approval

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
04/25/2000 BUILDING PRE-SLAB Partial Approval IVRS - Inspection 0000*1. INCORRECT HOLDDOWNS INSTALLED PLAN CALLS FOR HPAD22 HOLDDOWNS --PAHD42 HOLDDOWNS INSTALLED. HAVE PLANS REVISED TO AS BUILT OR CORRECTED TO MEET REQUIREMENTS. 2. ROUGH PLUMBING MUST BE 12" BELOW GRADE BY FOOTING. NOTE: PORCH X POST FOOTERS OK. ROUGH PLUMBING WATER TEST OK UNDER SLAB. SLAB STEEL OK.