Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Correction Required |
ADDTL COMMS - APPROVED AS NOTED: 1. SHEARWALL TRANSFER AT GARAGE NEEDS TO BE NAILED 4 O.C. AT BOTTOM PLATE TO TOP PLATE WITH 16ds. 2. TC CLIPS ARE NOT NAILED PER MANUFACTURERS SPECS. 3. HOLD-DOWN AT REAR SLIDER NAILED TO TRIMMERS. 4. NO TRUSS CALCULATIONS ON JOB SITE. |