Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM00692
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2000 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. OK TO DRYWALL UPON BLDG INSPECTORS APP 4. NOTE: CLOSET RINGS HAVE NOT BEEN INSTALLED ON 1ST FL |
|
09/21/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1. GAS PRESSURE TEST GAGES ARE NOT READING CORRECTLY PLEASE REPLACE AND RE TEST SYSTEM 2ND FL WATER CLOSET NOT AT 15" MIN FROM RECEPTACLE OF CLOSET TO SIDE WALL RE TEST SOIL SYSTEM |