Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM00680
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/29/2000 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C/O MISSING OUTSIDE SECURITY LIGHTS OK TEMP C OF O |
|
12/27/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* WORKING CLEARENCES IN FRONT OF A/C UNITS LABEL AC UNITS DISCONNECTS LABEL DISCONNECT FOR LIGHTING MISSING OUTSIDE FIXTURES DISCONNECTING MEANS FOR AIR HANDLER GFI ON LIGHTING CIRCUIT SWITCH |
|
12/18/2000 | ELECTRIC - FINAL | Partial Approval | BLDG #1 OK TO CLEAR TEMP POWER UNITS 1101-THRU 1104 1204 THRU 1204 |