Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 03/06/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1. MECHANICAL NOT PER PLAN-REVISE PLAN TO AS BUILT. 2. OUTSIDE ELECTRIC OUTLET NOT ALLOWED ON BATHROOM CIRCUIT. 3. REVISE PLAN FOR ELECTRIC WH. 4. REVISE PLAN FOR ALL OVERSIZED WIRE. 5. SPA MUST BE ON A DEDICATED CIRCUIT. 6. MAKE UP ALL GROUNDS. 7. GROUND ALL METAL ELECTRIC BOXES. 8. FAN BOXES CANNOT BE SUPPORTED/SECURED BY NAILS. 9. YOU CANNOT CHANGE WIRE SIZE IN A CIRCUIT. YOU MUST BUILD TO PLAN OR REVISE PLAN TO AS BUILT AND HAVE APPROVED. |