Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/01/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
12/03/2001 BUILDING - FINAL Partial Approval 1) PARTIAL PENDING INSULATION, PT AND STUCCO CERTIFICATES
11/16/2001 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) GARAGE MECHANICAL ROOM CONDENSATE LINE 2) SEAL ALL PENETRATIONS AT MECHANICAL ROOM BASEMENT 3) CAP OFF GAS LINE AT BBQ
11/14/2001 BUILDING - FINAL Denied 1) GAS BOND WIRE MISSING OR NOT IN ACCESSIBLE LOCATION 2) ELECTRIC PANEL MUST BE LABELED FOR "NO WATER BOND" 3) DOUBLE LUGGING OF NEUTRAL WIRES NOT PERMITTED 4) RE NEW END OF ONE NEUTRAL WIRE THAT HAS BEEN OVER HEATED TO MUCH CLUTTER IN HOUSE TO INSPECT, STOPPED INSPECTION 5) WORKSPACE TO A/C DISCONNECTS DOES NOT MEET CODE